Section B: Application Parameters

B2 DC Braking

B1-08 Run Command Acceptance During Programming RUN CMD at PRG
As a safety precaution the drive will not respond to a change in the run command when the digital
operator is being used to set or adjust parameters.This parameter will allow the drive to accept or
reject a change in the run command when the digital operator is being used to change or adjust param-
eters.
<1110>
Setting
0
1
B2
DC Braking
B2-01 DC Braking Frequency (Zero Speed Level)
Setting Range:
Factory Default:
Sets the frequency at which DC injection braking (or initial excitation for flux vector control) starts, in
units of 0.1 Hz. When B2-01 < E1-09, DC injection braking starts from the minimum frequency refer-
ence (E1-09).
B2-02 DC Braking Current
Setting Range:
Factory Default:
DC injection braking current is set as a percentage of inverter rated current. In flux vector control
mode, initial excitation is performed according to the motor no-load current set in E2-03. This param-
eter should not be set unnecessarily high or motor overexcitation may occur.
16
Run command is disabled when drive is in the programming mode. (factory default)
Run command is enabled when the drive is in the program mode
0.0 to 10.0Hz
0.5Hz
B2-01
DC Injection
Braking Frequency
Figure 5 DC Injection Braking at Starting
0 to 100%
50%
Table 1:
Description
DCInj Start Freq
B2-03
DC Injection Braking
Time at Start
DCInj Current
Open Loop
V/f
V/f w/PG
Vector
A
A
A
B
B
B
B
B
B
VS-616G5 Programming Manual
Flux
Vector
A
B
-