H1-__ = "24"
· PID Integral reset (Set value = 30)
Open: PID Integral values are added.
Closed: PID Integral value is set to zero.
· PID Control Integral Hold (Set value = 31)
Closed: Integral value of the PID control is held.
· DC Injection Braking Command (setting: "60")
When a DC injection braking command is input while the inverter is stopped, DC injection braking
operation is activated. When a run command or a jog command is input, DC injection braking is
released to start operation (operation has priority).
DC Injection Braking Command
VS-616G5 Programming Manual
Depress the Data/Enter key.
Input Level Selection
Depress
Detection Method
∧
the
key.
External Fault Action
OFF
Fwd Run Command
OFF
DC Injection
Braking
Output Frequency
Figure 35 DC Injection Braking Contact Input Timing Diagram
Section H: Control Circuit Terminals
N.O. Contact
N.C. Contact
Always
During Run
Ramp to Stop
Coast to Stop
Fast-stop
Alarm Only
<1110>
ON
ON
DC Injection
Braking
DC Injection Braking
Start Frequency
(B2-01)
H1 Digital Inputs
Open Loop
V/f
V/f w/PG
Vector
OFF
OFF
Flux
Vector