L1 Motor Overload - YASKAWA VS-616G5 Series Programming Manual

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

When operating several motors with one inverter, install a thermal relay on each motor. In this case, set
parameter L1-01 to "0".
L1-02 Motor Protection Time Constant
Setting Range:
Factory Default:
Sets the amount of time that the motor withstands 150% overload, when the motor is operated continu-
ously at rated current. This value should be set according to the overload resistance of motors used.
(when L1-02 = "1.0")
Notes:
1. If the motor is running at 100% output current or less, the electronic thermal overload relay
will not trip. (continued next page)
2. If the motor is run continuously at 150% output current, the electronic thermal overload relay
will trip after one minute if the motor is started "hot", and after eight minutes if the motor is
started "cold".
L2
Power Loss Ridethrough
When momentary power loss occurs, operation can restart automatically, according to the setting of
the following parameters.
L2-01 Momentary Power Loss Ridethrough Selection
Selects whether the inverter stops when power loss is detected or "rides through" a momentary power
loss. When ridethrough operation is selected, speed search starts from the current output frequency.
Setting
VS-616G5 Programming Manual
0.1 to 20.0 minutes
8.0 minutes
min
10
7
3
Operating
Time
1
0.4
0
Figure 49 Electronic Thermal Overload Curve
0
Momentary power loss ridethrough is disabled (factory default).
When momentary power loss is detected, a fault contact trips,
stopping the inverter.
1
Momentary power loss ridethrough is enabled, for the time set in
L2-02. When momentary power loss is detected, a fault contact
does not trip. If power is not restored within the time set in L2-02, a
fault contact trips, stopping the inverter.
MOL Time Const
<1110>
"Cold" Start
"Hot" Start
150
100
200
Motor Rated Current (E2-01)
PwrL Selection
Description
Section L: Protection Parameters

L1 Motor Overload