D2
Reference Limits
D2-01 Frequency Reference Upper Limit
Setting Range:
Factory Default:
The frequency reference upper limit is set as a percentage of the maximum output frequency (E1-04)
in increments of 1%.
D2-02 Frequency Reference Lower Limit
Setting Range:
Factory Default:
The frequency reference lower limit is set as a percentage of the maximum output frequency (E1-04)
in increments of 1%. When a run command is input and the frequency reference is less than the lower
limit, operation continues at the frequency reference lower limit. However, when the lower limit is set
to less than the minimum output frequency (E1-09), operation discontinues.
D3
Jump Frequencies
D3-01 Jump Frequency Reference 1
D3-02 Jump Frequency Reference 2
D3-03 Jump Frequency Reference 3
D3-04 Jump Frequency Reference Bandwidth
This function allows the prohibition or "jumping" of critical frequencies so that the motor can operate
without resonant vibrations caused by some machine systems. This function is also used for dead-band
control. Setting the value to 0.0Hz disables this function.
VS-616G5 Programming Manual
0.0 to 110.0%
100.0%
0.0 to 109.0%
100.0%
%
100
Internal
Frequency
Reference
0
Set Frequency Reference
Figure 25 Setting Frequency Upper and Lower Limits
D2 Reference Limit / D3 Jump Frequency
Ref Upper Limit
Ref Lower Limit
D2-01
D2-02
Hz
E1-04
Jump Freq 1
Jump Freq 2
Jump Freq 3
Jump Bandwidth
Section D: Reference Parameters
Open Loop
V/f
V/f w/PG
Vector
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
Flux
Vector
B
B
B
B
B
B
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents