YASKAWA VS-616G5 Series Programming Manual page 64

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

Section F: Option Parameters
F1 PG Option Set-up
F1-03 Overspeed Detection Stopping Method
Selects the stopping method when an overspeed condition is detected.
Setting
F1-04 PG Deviation Detection Stopping Method
Selects the stopping method when excessive speed deviation is detected.
Setting
F1-05 PG Rotation Selection
Sets the relationship between the motor rotation direction and PG polarity.
Setting
The motor rotation direction applies when viewing the motor shaft from the load side.
F1-06 PG Division Rate (pulse output)
Setting Range:
Factory Default:
Sets the division ratio for monitoring the PG pulse signals.
64
0
Ramp to stop - according to C1-02
1
Coast to stop (factory default)
2
Fast-stop according to C1-09
3
Alarm flashes, operation continues (this setting is disabled
during flux vector control)
0
Ramp to stop - according to C1-02
1
Coast to stop
2
Fast-stop according to C1-09
3
Alarm flashes, operation continues (factory default)
0
Motor FWD direction is counterclockwise (factory default).
1
Motor FWD direction is clockwise.
1 to 132
1
PG Overspeed Sel
Description
PG Deviation Sel
Description
PG Rotation Sel
Description
PG Output Ratio
VS-616G5 Programming Manual
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
B
B
B
B
B
B
B
B