YASKAWA VS-616G5 Series Programming Manual page 69

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

F4-01 Setting
18
Motor secondary current (Iq)
19
Motor excitation current (Id)
20
SFS output frequency
21
ASR input
22
ASR output
23
Speed deviation
24
PID feedback
25
Not Used
26
Voltage reference (Vq output)
27
Voltage reference (Vd output)
28-30
Not Used
31
Not Used
32
ACR(q) Output
33
ACR(d) Output
34-35
Not Used
36
PID Input Monitor
37
PID Output Monitor
38
PID Setpoint or Reference
F4-02 Analog Output Channel 1 Gain
Setting Range:
Factory Default:
Sets the channel 1 output gain for the analog output monitors. To obtain the output level, multiply the
monitor output level by the gain value set in F4-02.
VS-616G5 Programming Manual
Analog Output Channel 1 Selection (Continued)
Function
Monitors the calculated value of the motors secondary current. (Iq) The motors
rated secondary current corresponds to 100%. 10 V=Rated secondary current.
(0 to + 10 V output)
Monitors the calculated value of the motors excitation current. (Id) The motors
rated excitation current corresponds to 100%. 10 V=Rated excitation current. (0
to + 10 V output).
Monitors the output frequency after a soft start. This is the frequency without the
correction from compensation functions such as slip compensation. 10 V=Max.
frequency (0 to +/- 10 V possible)
Monitors the input to the speed control loop. The max. frequency corresponds to
100%. 10 V=Max. frequency (0 to +/- 10 V possible)
Monitors the output from the speed control loop. Analog monitor becomes 10 V/
max. output frequency with V/F control. In vector control the analog monitor be-
comes 10V= motor rated excitation current. (0 to +/-10V possible.)
Monitors the speed deviation within the speed control loop. The max. frequency
corresponds to 100%. 10 V=Max. frequency (0 to +/-10 V possible.)
Monitors the feedback value when the PID control is utilized. The input for the
max. frequency corresponds to 100%. 10 V= Max frequency.
(0 to +/-10 V possible.)
Monitors the inverters internal voltage reference value for the motors secondary
current control. 10 V= 200,400 or 575 VAC (0 to =/- 10 V possible.)
Monitors the inverters internal voltage reference value for the motors excitation
current control. 10 V= 200,400 or 575 VAC (0 to =/- 10 V possible.)
Monitors current control output value for the motors secondary current.
10 V= 100%.
Monitors current control output value for the motors excitation current.
10 V= 100%.
Monitors the input to the PID circuit. This is the PID reference + the PID reference
bias - the PID feedback. 10 V= Max frequency.
Monitors the output of the PID circuit. 10 V= Max frequency.
Monitors the PID setpoint. This is the PID setpoint + the PID setpoint bias.
10 V= Max frequency.
0.00 to 2.50
1.00
F4 AO-08/AO-12 Option Set-up
Description
--
--
--
--
AO CH1 Gain
Section F: Option Parameters
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
A
A
A
A
69