Motor and V/f Pattern Setup

Setting Motor Parameters

In vector control method, the motor parameters are set automatically during autotuning (refer to
Autotuning
Related Parameters
Parameter
No.
E2-01
E2-02
E2-03
E2-04
E2-05
E2-06
E2-07
E2-08
E2-10
E2-11
E2-12
Note All factory-set parameters are for a Yaskawa standard 4-pole motor.
* The factory settings depend on Inverter capacity (the values shown are for a 400 V Class Inverter for 3.7 kW).
Manual Setting of the Motor Parameters
Motor Rated Current Setting (E2-01)
Set E2-01 to the rated current value on the motor nameplate.
Motor Rated Slip Setting (E2-02)
Set E2-02 to the motor rated slip calculated from the number of rated rotations on the motor nameplate.
Motor No-Load Current Setting (E2-03)
Set E2-03 to the motor no-load current at the rated voltage and rated frequency. Normally, the motor no-load
current is not written on the motor nameplate. Consult the motor manufacturer.
Factory setting is the no-load current value for a standard Yaskawa 4-pole motor.
Number of Motor Poles Setting (E2-04)
E2-04 is displayed only when Closed Loop Vector control method is selected. Set the number of motor poles
as written on the motor nameplate.
-50
5
Mode. If autotuning does not complete normally, set them manually.
Name
Motor rated current
Motor rated slip
Motor no-load current
Number of motor poles (Number of poles)
Motor line-to-line resistance
Motor leak inductance
Motor iron saturation coefficient 1
Motor iron saturation coefficient 2
Motor iron loss for torque compensation
Motor rated output power
Motor iron saturation coefficient 3
Motor rated slip = Motor rated frequency (Hz) –
Factory
Setting
14.00 A *
2.73 Hz *
4.50 A *
4 poles
0.771 Ω *
19.6 %
0.50
0.75
112 W *
3.700 *
1.30
Rated speed (rpm) x No. of motor poles
http://nicontrols.com
page 3-12,
Control Methods
Change
Open
Closed
during
V/f
Loop
Operation
Vector
Vector
No
Q
Q
No
A
A
No
A
A
No
No
Q
No
A
A
No
No
A
No
No
A
No
No
A
No
A
No
No
Q
Q
No
No
A
120
Loop
Q
A
A
Q
A
A
A
A
No
Q
A