F2 Ai-14 Set-Up - YASKAWA VS-616G5 Series Programming Manual

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

F1-14 PGO Detection Time
Setting Range:
Factory Default:
Parameter F1-14 sets the time from when the pulse generator (PG) signal is missing to when the fault
signal is displayed.
The stopping method when a "PGO" fault is detected is selected by parameter F1-02.
If a speed reference is commanded, but the motor is physically locked, a "PGO" fault will occur even
though the PG is not disconnected from the inverter.
F2
AI-14B Set-up
F2-01 Bipolar or Unipolar Input Selection
Sets CH1 to CH3 input functions when AI-14B option is connected.
Setting
0
input (factory default)
1
3-channel additional
When the 3CH individual input is used, parameter B1-01 is automatically set to "l" (frequency refer-
ence from control circuit terminal). The option/inverter reference selection, which is selected by a
multi-function contact input (H1-__ = "2"), is disabled when using the AI-14B option.
VS-616G5 Programming Manual
0.0 to 10 seconds
2 seconds
Function
CH1 (TC1 to TC4) CH2 (TC2 to TC4) CH3 (TC3 to TC4)
3-channel individual
terminals 13 and 17
Sum of CH1 to CH3 input values is used as the frequency
input
reference value.
PGO Detect Time
AI-14 Input Sel
Substitute for
Substitute for
terminals 14 and 17
Section F: Option Parameters
F2 AI-14B Option Set-up
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
A
A
A
A
A
A
Substitute for
terminals 16 and 17
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents