A2 User's Parameters; B Application Parameters; B1 Sequence - YASKAWA VS-616G5 Series Programming Manual

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

A2
User's Parameters
The user can select up to 32 parameters for quick-access programming. By setting the user access level
(A1-01) to "User Program", only the parameters selected in function A2 can be accessed by the user.
Parameter A1-01 must be set to 4 (advanced access level) to input parameter numbers into A2-01
through A2-32, and then A1-01 must be set to 1 (User Level) for only the user selected parameters to
be viewed.
Main Menu: Programming
B
Application Parameters
B1
Sequence
B1-01 Frequency Reference Selection
B1-02 Operation Method Selection
Frequency reference and run command can be set independently as shown below:
Setting
*
Setting parameter B1-01 or B1-02 to 4 allows reference and/or run source from CP-717 when
either CP-916 or CP-216 option cards are installed.
By depressing the LOCAL/REMOTE key on the digital operator, the operation mode can be
selected as shown below:
Local:
Remote: Operation according to frequency reference and run command set by B1-01 and B1-
The digital operator is reset to remote operation when power is cycled.
VS-616G5 Programming Manual
<ENTER>
0
Command from digital operator
1
Command from control circuit terminal (factory default)
2
Command from serial communication
3
Command from option card
4
EWS (Reference from CP-717)*
This setting will be used with the CP-717 to run and change
the reference through DP-RAM.
Operation according to frequency reference and run command from digital operator.
02.
Section B: Application Parameters
A2 User Parameters and B1 Sequence
Reference Source
Run Source
Description
<1110>
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
Q
Q
Q
Q
Q
Q
Q
Q
11