L5-02 Automatic Restart Operation Selection
Selects whether a fault contact output is activated during automatic restart.
Setting
L6
Torque Detection
The overtorque detection circuit activates when the motor load causes the motor current (or torque dur-
ing vector control) to exceed the overtorque detection level (L6-02). When an overtorque condition is
detected, alarm signals are sent to multi-function output terminals 9, 25 and 26.
To output an overtorque detection signal, select torque detection 1 at either of the multi-function con-
tact outputs (H2-__ = "B" or "17"). Refer to section H2, Digital Outputs on page 88, for more details.
Multi-function Contact
Output Signal
(Overtorque Detection Signal)
Terminal 9, 25, 26
* Release width (hysteresis) during overtorque detection is 5% of the inverter rated current level.
L6-01 Overtorque Detection 1 Selection
Activates overtorque detection, and selects whether detection generates an alarm or a fault.
Setting
0
Overtorque detection is disabled (factory default).
1
Overtorque detection is enabled whenever at the speed agree level (when inverter is not
accelerating or decelerating). Continue running after detection (OL3 alarm).
2
Overtorque detection is enabled always. Continue running after detection (OL3 alarm).
3
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after
detection (OL3 fault).
4
Overtorque detection is enabled always. Coast to a stop after detection (OL3 fault).
L6-01 Notes:
1. To detect torque during acceleration or deceleration, set to "2" or "4".
2. To continue operation after overtorque detection, set to "1" or "2". During detection, the digital
operator displays an "OL3" alarm (blinking).
3. To stop the inverter after an overtorque detection fault, set to "3" or "4". During detection, the dig-
ital operator displays an "OL3" fault.
VS-616G5 Programming Manual
0
No fault relay (factory default)
1
Fault relay active
Inverter Rated Current
L6-02
Figure 55 Overtorque Characteristics Timing Diagram
Restart Sel
Description
Motor Current
*
*
ON
ON
L6-03
L6-03
Torq Det 1 Sel
Description
Section L: Protection Parameters

L6 Torque Detection

B
B
B
Time
B
B
B
B
B
113