YASKAWA VS-616G5 Series Programming Manual page 10

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

Section A: Initialization Parameters
A1 Initialization Set-up
A1-03 Operator Status
Use this parameter to reset the inverter to its factory default settings. Initialize the inverter after chang-
ing the control PCB, or after selecting language (A1-00), control method (A1-02), or inverter capacity
(O2-04).
Setting
A1-04 Password Entry
Parameter A1-04 is used to enter a password into the inverter, to be able to make adjustments to locked param-
eters.
Password protection is provided for:
A1-01 Access Level
A1-02 Control Method
A1-03 Initialization
A2-01 to A2-32 User Parameters (If selected)
10
0
No Initialization (factory default)
1110
User Initialization - resets the inverter to user-specified initial
values. To set user-specified initial values, make all required
changes to parameter settings, then set O2-03 to "1". The
inverter will memorize all current settings as the user-specified
initial values. Up to 50 changed parameters can be stored.
2220
2-Wire Initialization - terminal 1 becomes FWD run command
and terminal 2 becomes REV run command. All other param-
eters are reset to their original factory default settings.
3330
3-Wire Initialization - terminal 1 becomes run command, termi-
nal 2 becomes stop command and terminal 3 becomes FWD/
REV run selection. All other parameters are reset to their orig-
inal factory default settings.
Init Parameters
Description
Enter Password
VS-616G5 Programming Manual
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
Q
Q
Q
Q
Q
Q
Q
Q

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents