F7 Po-36F Set-Up; F8 Si-F/G Option Set-Up - YASKAWA VS-616G5 Series Programming Manual

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

F7
PO-36F Set-up
The PO-36F option card outputs pulse signals that correspond to the inverter output frequency. These
signals are used in master/slave configurations where speed matching is needed.
.
F7-01 PO-36F Pulse Monitor Output Selection
Sets the number of pulse signals to be output from the PO-36F option.
F8
Function F8 SI-F/G Set-up
The setting of parameter F8-01 selects the stopping method when an E-15 fault is detected.
F8-01 (E-15) Detection Stopping Method
An E-15 fault may occur when using the SI-F or SI-G communication options. The fault will occur
after initial communication has been established then the connection is lost. The following fault code
will be displayed:
VS-616G5 Programming Manual
Setting
0
Inverter output frequency × 1
1
Inverter output frequency × 6 (factory default)
2
Inverter output frequency × 10
3
Inverter output frequency × 12
4
Inverter output frequency × 36
Setting
0
Ramp to stop according to C1-02 set value
1
Coast to stop.
2
Ramp to stop according to C1-09 set value.
3
Alarm flashes, operation continues.
F7 PO-36F & F8 SI-F/G Option Set-up
PO-36F Selection
Number of Output Pulses
E-15 Det Sel
Description
Section F: Option Parameters
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
A
A
A
A
A
A
A
A
73