Section B: Application Parameters
B1 Sequence
· Coast to Stop with Timer 1 (B1-03 = "3 ")
Output Frequency
FWD (REV)
Run Command
After a stop command is given, a run command is not accepted while the coast to stop timer elapses
(same as Decel 1). After the timer runs out, another run command must be given for the inverter to
begin acceleration. This stopping method is disabled during flux vector control.
B1-04 Prohibition of Reverse Operation
A "reverse run disabled" setting does not allow a reverse run command from the control circuit termi-
nal or the digital operator. This setting is used in applications where a reverse run command is undesir-
able.
Setting
14
Coasting
ON
Run Command Disabled
Figure 4 Stopping Method - Coast to Stop w/ Timer
0
Reverse run enabled (factory default)
1
Decel Time 1
(C1-02)
ON
ON
Reverse Oper
Description
Reverse run disabled
Open Loop
V/f
V/f w/PG
Vector
Accel Time 1
(C1-01)