YASKAWA VS-616G5 Series Programming Manual page 121

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

O1-02 Monitor Selection After Power-up
Selects the monitor to be displayed on the digital operator immediately after the power supply is turned
ON.
O1-03 Scale for Setting and Monitoring Frequency
Units for parameters and monitors related to frequency can be scaled as shown below.
Setting
00000
00001
00002 to 00039
00040 to 03999
(user-selected units)
VS-616G5 Programming Manual
Setting
1
Displays frequency reference (factory default).
2
Displays output frequency.
3
Displays output current.
4
Displays the monitor set in O1-01.
Unit: 0.01Hz (factory default)
Unit: 0.01%
Unit: rpm (0 to 3999)
Digits:
5th
4th
0
0
The 1st thru 4th digits determine the set value at 100% output frequency.
Decimal point position is set by the 5th digit as follows:
5th digit = 0: displayed as 0000
5th digit = 1: displayed as 000.0
5th digit = 2: displayed as 00.00
5th digit = 3: displayed as 0.000
Example 1
If 100% output frequency is equal to 200.0 units:
Set O1-03 = "12000"; 100% of this reference is displayed as 200.0 and 60%
of this reference is displayed as 120.0.
Example 2
If 100% output frequency is equal to 65.00:
Set O1-03 = "26500"; 60% of this reference is displayed as 39.00.
Power-On Monitor
Description
Display Scaling
Description
3rd
2nd
1st
0
0
0
Section L: Operator Parameters
O1 Monitor Selection
B
B
B
B
B
B
B
B
121