Appendix
VS-616G5 Parameter List L Protection
Name
Parameter
Function
(Digital Operator
No.
Display)
Internal DB
Resistor
L8-01
Protection Selection
(DB Resistor Prot)
Overheat Pre-alarm
L8-02
Level
(OH Pre-Alarm Lvl)
Operation Selec-
tion after OH Pre-
L8-03
alarm
(OH Pre-Alarm Sel)
Input Phase Loss
L8-05
Protection
(PH Loss In Sel)
Output Phase Loss
L8-07
Protection
(PH Loss Out Sel)
Short-circuit
L8-10
Protection Selection
(Ground Fault Sel)
IGBT Protection
L8-17
Selection at Low
Frequency
(Prtct@L - Spd)
OL2 Characteris-
tics Selection at
L8-19
Low Speed
<1110>
(OL2 Chara@L-
Spd)
154
Setting
Setting
Factory
Range
Unit
Setting
(Digital Operator Display)
0: (Not Provided)
0, 1
1
0
1: (Provided)
*Factory setting depends on
1 deg C 95 C*
inverter model [02-04].
50~130
0: (Ramp to Stop) using C1-02
1: (Coast to Stop)
0~3
1
3
2: (Fast-Stop) using C1-09
3: (Alarm Only) display flashes
0: (Disabled)
0, 1
1
0
1: (Enabled)
0: (Disabled)
1: (Enabled)
0, 1
1
0*
*When 02-09=1, the factory
default setting is 1.
0: (Disabled)
0, 1
1
1
1: (Enabled)
0: Conventional
1: (Lower fc)
decreased when fout ≤
10Hz and the load is >
100% iac.
2: (Short term OL2)
OL occurs after 2 seconds
during low speed [fout £
0, 1
1
1*
6Hz] current limit.
3: (I-Limit=150%)
of the inverter rated current.
< G5 plus > Addition
* When 02-09=1 factory set-
ting is 1.
* When 02-09=2 factory set-
ting is 2.
0: (Disabled)
Low frequency OL disabled
0, 1
1
0
1: (Enabled)
Low frequency OL enabled
Change
during
Remarks
Operation
o: Enabled
x: Disabled
OH Heatsink Ovrtemp
Carrier frequency is
Current limit is set to 150%
Parameter Access Level
V/f
Open
V/f
w/
Loop
PG
Vector
x
B
B
B
x
A
A
A
x
A
A
A
x
A
A
A
x
A
A
A
x
A
A
A
x
A
A
A
x
A
A
A
VS-616G5 Programming Manual