YASKAWA VS-616G5 Series Programming Manual page 89

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

H2-01
to 3
Setting
5
Frequency detection 2
6
Inverter ready
7
DC bus undervoltage
8
Baseblock 1
9
Option reference
A
Remote operation
B
Torque detection 1 (N.O.)
C
Loss of reference
D
DB overheat
E
Fault
F
Not used
10
Minor fault
11
Reset command active
12
Timer output
13
Frequency agree 2
14
Desired frequency agree 2
15
Frequency detection 3
16
Frequency detection 4
17
Torque detection 1 (N.C.)
18
Torque detection 2 (N.O.)
19
Torque detection 2 (N.C.)
1A
Reverse direction
1B
Baseblock 2
1C
Motor 2 Selection
1D
Regenerating
1E
Restart enabled
1F
Overload (OL1)
20
OH pre-alarm
30
Current/torque limit
31
Speed limit
33
Zero servo completion
37
During run 2
· During Run (setting: "0")
Closes when a run command is input, or when the inverter outputs voltage.
· Zero-speed (setting: "1")
Closes when the inverter output frequency is less than the minimum output frequency (El-09) during
V/f control with PG feedback. Closes when the motor speed is less than the zero-speed level (B2-01)
during flux vector control.
VS-616G5 Programming Manual
Function
Control Method (A1-02)
Open Loop
V/f
V/f w/ PG
Vector
Section H: Control Circuit Terminals
H2 Digital Outputs
Reference
Page
Flux Vector
89