System Parameters; Control Command - YASKAWA PVI 60TL Installation And Operation Manual

Table of Contents

Advertisement

4.4.2.1 System Parameters

(1) "Language Setting" One language, i.e. English is available in "Language" menu.
(2) "Grid Rule": There are four grid standards. Selecting the corresponding grid
standard and press ENT confirm the selection as shown in Figure 4-9.
INSTRUCTION:
Please check with your local electricity supply company before selecting
the grid standard. If the inverter is operated with a wrong grid standard,
the electricity supply company may cancel the operation license.
Putting the inverter into operation before the overall system complies with
the national rules and safety regulation of the application is not permitted.
(3) "PV Input Mode": The inverter can work only under "Independent Mode"
(4) "Com Setting": In this interface you can set the address and baud rate for
communication.
(5) "Time": Move the cursor to the "Time" set the system time. Press "
"
" set the value, then press "ENT" to move to the next option. e.g.: Year to
Month. Finally Press "ENT" to confirm your selection.
(6) "LCD Contrast Setting": Setting the LCD contrast grade.

4.4.2.2 Control Command

There are 8 submenus in the "Control Command":
(1) "Restart" menu: If a fault shutdown happens, a severe fault may have occurred
inside the inverter. The user can perform a manual reboot once using this menu if
the user needs to restart the inverter.
INSTRUCTION:
This function is effective only when the fault "IntFault0010~0150" in the
troubleshooting table occurs. The inverter may return to normal operation
DOCR-070645-E
Grid Connection Rule
IEEE1547
Rule-21
HECO-HM
HECO-ML
Figure 4-9 Setting Grid Rule
" or
Page 64 of 102