11.4.2 Description Of The Default Settings - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

Programming the user functions

11.4.2 Description of the default settings

Step
Function
1
Change the activated time of control line 4
Change the function of control line 5
2
Change the flooding time of control line 4
Change the flooding time of control line 5
3
Change the function of contact 1
Change the function of contact 3
Change the function of contact 2
Change the function of LED9 (Remote
transmission) and LED6 (Fire alarm)
Change the function of control line 2
4
Change the function of monitored input 1
Suppress the fault indication if state "Released" is
not reported
Change the function of monitored input 2
5
Change the active mode of control line 1
Change the active period of control line 1
Change the active mode and active period of
control line 3
6
Enable "Alarm verification" function of detector
zones 1 and 2
Enable "Alarm verification" function of detector zone
3
Enable "Alarm verification" function of detector zone
4
7
Deleted
Deleted
Deleted
8
Change the function of monitored input 3
Suppress "Reset" upon stopped activated time by
the monitored input 3
Change the fault processing of the monitored input
3
72
Building Technologies
Fire Safety & Security Products
Default settings for standard applications are based on EN54-2 and EN12094-1.
Default
setting
7
14
1
6
1
5
8
10
12
15
17
1
4
6
1
5
9
11
15
18
20
1
3
5
1
7, 9
11
1
8
10
Default value
Activated time 30 seconds
Active in state "Activated" but activated time 0 seconds
Processing as "Actuator"
Flooding time 30 seconds
Flooding time 30 seconds
Active during "Released" to "Reset" state
Active with "Fire alarm" to "Reset" state
Active during "Fault" to "Silence Buzzer" state
Immediate triggering
LED9: Active only in "RT-alarm" state
LED6: Active on Alarm Z1 or Z2 or Z3
Active on state "RT-alarm" to "Reset"
Processing as "RT-alarm"
State "Active 1" (680 ) = "Released"
State "Active 2"(1k2) = "Loss of agent"
State "Open" or "Short circuit" = "Fault"
Fault if state "Released" is not reported within 30sec after control
line 4 has been activated
State "Active 1" (680 ) = "Mech. Blocked"
State "Active 2" (1k2) = "Normal" (not mech. blocked)
State "Active 1 + 2" or "Inactive 1 + 2" = "Fault" (LED2 flashing)
State "Open" or "Short circuit" = "Fault"
State "Fire alarm" = continuous
State "Activated" = pulsating fast and pulsating slow in state
"Emergency hold or abort"
State "Released" = pulsating
Active until "Silence Re-sound Horn" and "Reset"
State "Fire alarm" = not activated
State "Activated" = continuous
State "Released" = continuous until "Reset"
No alarm verification
No alarm verification
No alarm verification
Not applicable
Not applicable
Not applicable
In state "Activated":
State "Active 1" (680 ) =
LED26 lights up
Activated time is stopped
Horn turns to "Hold/Abort" tone
State "Active 1" cancelled = Abort remains active until reset
In state "Normal":
State "Active 1" (680 ) =
LED26 lights up
Block the activated process. When
new alarm happens, system enters
fire alarm state and horn turns to
"Hold/Abort" tone
State "Active 1" cancelled = Abort remains active until reset
Function "Reset" available
State "Short circuit" and "Open" = "Fault" + "Emergency
hold/abort" state
A6V10099837_a_en