Function block End-user space
heating
This function block contains settings and readouts that are intended for the end-user.
5.1

Operating lines

The buttons for selecting the operating lines and for adjusting the settings are de-
scribed in section 22.1 "Operation".
Line
Function, parameter
1
Current nominal room temperature setpoint
2
Reduced room temperature setpoint
3
Frost protection / holiday mode setpoint
5
Heating curve slope
6
Weekday for entering the heating program
7
Heating period 1 start
8
Heating period 1 end
9
Heating period 2 start
10
Heating period 2 end
11
Heating period 3 start
12
Heating period 3 end
* The variable setting ranges are defined in the following sections
5.2

Settings and displays

• The nominal room temperature setpoint is set with the setpoint knob. Its scale is
calibrated in °C room temperature. The room temperature is maintained at that set-
point:
In automatic mode during the heating periods
In continuous operation at all times
• On operating line 1, the LCD displays the current setpoint, depending on the operat-
ing mode and the operating state:
Operating mode or operat-
ing state
Heating to nominal setpoint
Heating to reduced setpoint
Continuous operation
Quick setback
Frost protection mode
OFF by ECO
• The reduced room temperature setpoint is to be set on operating line 2. The setting
range is generated by the nominal room temperature setpoint and the setpoint for
frost protection. This setpoint is maintained outside the heating periods
• The setpoint for frost protection is to be set on operating line 3. The setting range lies
between 8 °C (fixed value) and the adjusted reduced setpoint. This frost protection
thus acts as frost protection of the building.
The setting also represents the setpoint for the holiday mode. A holiday program can
only be entered on the QAW70 room unit, however
• The d.h.w. temperature setpoint is to be set on operating line 4. Its setting range
depends on the type of plant. For detailed information, refer to section 16.5
"Maximum setpoint"
Basic Documentation RVD110, RVD130

5 Function block End-user space heating

Unit
Factory setting
Display function
°C
°C
Current weekday
hh:min
hh:min
hh:min
hh:min
hh:min
hh:min
Setpoint displayed
Adjustment made with the setpoint knob (incl. read-
justment made on the room unit)
Reduced setpoint (setting operating line 2)
Adjustment made with the setpoint knob
Reduced setpoint (setting operating line 2)
Setpoint for frost protection (setting operating line 3)
• During heating periods: Adjustment made with
the setpoint knob (incl. readjustment made on the
room unit)
• Outside the heating periods: Reduced setpoint
Range
14
variable*
8
8...variable*
15
2.5...40
1...7, 1-7
06:00
--:-- / 00:00...24:00
22:00
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
CE1P2381E
27.05.2004