2-11 Wiring of an external emergency stop

2-11-1 External emergency stop setting

Besides the emergency stop input from the NC communication cable (CN1A, CN1B), double-protection
when an emergency stop occurs can be provided by directly inputting an external emergency stop to the
CN23 connector on the power supply unit. Even if the emergency stop is not input from CNC for some
reason, the contactors will be shut off by the external emergency stop input from CN23 connector on the
power supply unit.
(1) Connection
Emergency
Mitsubishi NC
SV1,2
FCUA-R000
External emergency stop input
(2) Setting
When using the external emergency stop, the protection setting must be validated with the rotary
switch on the front of the MDS-C1-CV and the connected drive unit's parameter (PTYP).
Rotary switch setting
With external contactor ... Set
Parameter settings
Abbrevia-
No.
Parameter name
tion
SV036
PTYP
Power supply type
SP041
CAUTION
POINT
2. Wiring and Connection
MDS-C1-V1/V2/SP
stop
Alarm
CN1A
CN1B
SH21
CN4
.
4
When external emergency stop is validated, 0040 [hex] is added to PTYP for the drive
unit connected to the power supply unit.
The emergency stop signal input to the CNC side cannot be used as a substitute
for the external emergency stop function (CN23).
1. The parameter must be set for the CN23 external emergency stop function.
2. The emergency stop signal input to the CNC side cannot be used as a
substitute for the external emergency stop function.
MDS-C1-CV
Alarm
CN4
SH21
FCUA-R000
CN23
1 EMG1
2
NC
3 EMG2
Descriptions
2 - 44
MC1
MC1
Contactor shutoff
L
11
command
L
21