SRX240 Services Gateway Rack Requirements

Related
Documentation
Clearance Requirements for Airflow and Hardware Maintenance on the SRX240
Services Gateway
Copyright © 2015, Juniper Networks, Inc.
The SRX240 Services Gateway can be installed in a rack. Many types of racks are
acceptable, including front-mount racks and four-post (telco) racks.
Table 16 on page 33
provides the details on rack size, clearance, and airflow requirements.

Table 16: Rack Requirements for the Services Gateway

Rack Requirements
Specifications
Rack Size
A 19 in. (48.3 cm) rack as defined in Cabinets, Racks, Panels, and
Associated Equipment (document number EIA-310-D) published by the
Electronics Industry Association (
Rack Requirements
The outer edges of the mounting brackets extend the width of either
chassis to 19 in. (48.3 cm).
The front of the chassis extends approximately 0.5 in. (1.27 cm) beyond
the mounting ears.
Maximum permissible ambient temperature when two devices are
placed side by side in a 19 in. rack is 40
Spacing of Mounting
The holes within each rack set are spaced at 1 U. The device can be
Bracket and Flange
mounted in any rack that provides holes or hole patterns spaced at
Holes
1-U [1.75 in. (4.5 cm)] increments.
The mounting brackets and front-mount flanges used to attach the
chassis to a rack are designed to fasten to holes spaced at rack
distances of 1 U (1.75 in.).
The mounting holes in the mounting brackets provided with the device
are spaced 1.25 in. (3.2 cm) apart (top and bottom mounting hole).
Connecting to the
Always secure the rack in which you are installing the services gateway
Building Structure
to the structure of the building. If your geographical area is subject to
earthquakes, bolt the rack to the floor. For maximum stability, also secure
the rack to ceiling brackets.
General Site Guidelines for Installing the SRX240 Services Gateway on page 30
Clearance Requirements for Airflow and Hardware Maintenance on the SRX240 Services
Gateway on page 33
SRX240 Services Gateway Electrical and Power Requirements on page 36
When planning the installation site for the SRX240 Services Gateway, you need to allow
sufficient clearance around the rack.