2. Slide the backplane into the server system guides (see letter B).
3. Secure the backplane with the screw as shown (see letter C).
4. Connect cables to backplane, please refer to

Replacing the Lower Fan Board

Before removing or installing the lower fan board, please make sure following steps are performed.
1. Ensure the AC power cord(s) are disconnected from the system.
2. Remove the system cover. For instructions, see
3. Remove system the fan modules connected to the lower fan board. For instructions, see
a Redundant Fan
4. Remove the rack handles. For instructions, see
5. Remove the front end module. For instructions, see

Removing the Lower Fan Board

1. Disconnect all cables from the lower fan board.
2. Remove the screws (see letter A).
3. Remove the lower fan board from the server chassis (see letter B).
®
Intel
Server System R2000LH2/LT2 Service Guide

Figure 75. Installing the backplane

Module.
Hardware Installations and Upgrades
Cable
Routing.
Removing the System
Cover.
Removing the Rack
Handles.
Removing the Front End
Replacing
Module.
49