METREL MI 3122 Instruction Manual page 7

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD
RCD functions
Parameters set in one function are also kept for other RCD functions.
The Contact voltage test will normally not trip-out RCD of tested installation.
However, the RCD trip-out may occur and Uc measurement is affected as a result
of existing PE leakage currents in the installation.
RCD trip-out current and time will be measured only if the contact voltage - pretest
passed successfully.
L and N test terminals are reversed automatically according to detected terminal
voltage (except in UK version).
It can happen that the RCD trips-out during the safety pretests. Possible reasons for
trip-out are incorrect set RCD parameters (I
defective RCD.
Z-LOOP
The Z-LOOP impedance function will trip-out the RCD in RCD protected installation
that is tested. Use the Zs
The Zs
impedance function takes longer time to complete but has much better
rcd
accuracy then R
Specified accuracy of tested parameters is valid only if mains voltage is stable
during the measurement.
L and N test terminals are reversed automatically according to detected terminal
voltage (except in UK version).
Z-LINE
In case of measurement of Z
connected together the instrument will display a warning of dangerous PE voltage.
The measurement will be performed anyway.
Specified accuracy of tested parameters is valid only if mains voltage is stable
during the measurement.
L and N test terminals are reversed automatically according to detected terminal
voltage (except in UK version).
impedance function to prevent the trip-out.
rcd
sub-result in RCD: Uc function.
L
Line-Line
), existing leakage currents or
N
with the instrument test leads PE and N
7
Warnings and notes