METREL MI 3122 Instruction Manual page 33

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD
Line to neutral
Figure 5.13: Examples of line impedance measurement result
Displayed results:
Z .............. Line impedance,
I
............ Prospective short-circuit current,
SC
Lim .......... Low limit prospective short-circuit current value or high limit line
impedance value for the UK version.
Prospective short circuit current is calculated as follows:
where:
Un ........ Nominal L-N or L1-L2 voltage (see table below),
ksc ....... Correction factor for Isc (see chapter 4.2.6 ).
Note:
High fluctuations of mains voltage can influence the measurement results (the noise
sign
is displayed in the message field). In this case it is recommended to repeat
few measurements to check if the readings are stable.
UK version
Un
I
SC
U
Input voltage range (L-N or L1-L2)
n
110 V
(93 V  U
(185 V  U
230 V
400 V
(321 V  U
Line to line
k
SC
Z
 134 V)
L-N
 266 V)
L-N
 485 V)
L-L
33
Line impedance