MI 3122 Smartec Z Line-Loop / RCD
Voltage measurement procedure
Select the
VOLTAGE TRMS
Connect test cable to the top of the instrument.
Connect test leads to the item to be tested (see figures 5.15 and 5.16 ).
Store current measurement result by pressing the MEM key (optional).
Measurement runs immediately after selection of
Figure 5.17: Examples of voltage measurement in three-phase system
Displayed results for single phase system:
Uln ........... Voltage between phase and neutral conductors,
Ulpe ......... Voltage between phase and protective conductors,
Unpe ........ Voltage between neutral and protective conductors,
f ............... frequency.
Displayed results for three-phase system:
U12 .......... Voltage between phases L1 and L2,
U13 .......... Voltage between phases L1 and L3,
U23 .......... Voltage between phases L2 and L3,
1.2.3 ........ Correct connection – CW rotation sequence,
3.2.1 ........ Invalid connection – CCW rotation sequence,
f ............... frequency.
Voltage, frequency, phase sequence
function using the function selector switch.
VOLTAGE TRMS
35
function.