Trip-Out Current (Rcd I); Rcd Autotest - METREL MI 3122 Instruction Manual

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD

5.1.3 Trip-out current (RCD I)

A continuously rising residual current is intended for testing the threshold sensitivity for
RCD trip-out. The instrument increases the test current in small steps through appropriate
range as follows:
RCD type
AC
A (I
A (I
Maximum test current is I
Trip-out current measurement procedure
Select the
RCD
Set sub-function RCD I.
Set test parameters (if necessary).
Connect test cable to the top of the instrument.
Connect test leads to the item to be tested (see figure 5.2 ).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional).
Trip-out
Figure 5.5: Trip-out current measurement result example
Displayed results:
I .......... Trip-out current,
Uci ...... Contact voltage at trip-out current I or end value in case the RCD didn't trip,
t .......... Trip-out time.

5.1.4 RCD Autotest

RCD autotest function is intended to perform a complete RCD test (trip-out time at different
residual currents, trip-out current and contact voltage) in one set of automatic tests, guided
by the instrument.
Additional key:
HELP / DISPLAY
Start value
0.2  I
 30 mA)
0.2  I
N
0.2  I
= 10 mA)
N
(trip-out current) or end value in case the RCD didn't trip-out.
function using the function selector switch.
Toggles between top and bottom part of results field.
Slope range
End value
1.1  I
N
N
1.5  I
N
N
2.2  I
N
N
After the RCD is turned on again
27
Testing RCD
Waveform
Sine
Pulsed