Line Impedance And Prospective Short-Circuit Current - METREL MI 3122 Instruction Manual

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD

5.3 Line impedance and prospective short-circuit current

Line impedance is measured in loop comprising of mains voltage source and line wiring. It
is covered by requirements of the EN 61557-3 standard.
See chapter 4.1 Function selection for instructions on
key functionality.
Test parameters for line impedance measurement
FUSE type
Selection of fuse type [---, NV, gG, B, C, K, D]
FUSE I
Rated current of selected fuse
FUSE T
Maximum breaking time of selected fuse
Lim
Minimum short circuit current for selected fuse.
See Appendix A for reference fuse data.
Connections for measurement of line impedance
Ro
R
E
Figure 5.12: Phase-neutral or phase-phase line impedance measurement – connection of
Line impedance measurement procedure
Select the
Z-LINE
Select test parameters (optional).
Connect test cable to the top of the instrument.
Connect test leads to the item to be tested (see figure 5.12 ).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional).
plug commander and universal test cable
function using the function selector switch.
Figure 5.11: Line impedance
N
32
Line impedance
PE
L
L1
L2
L3
N
PE