Initial Settings - METREL MI 3122 Instruction Manual

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD

4.2.2 Initial settings

Selecting this option will allow the user to reset
the instrument settings and measurement
parameters and limits to the manufacturers
standard values.
Keys:
TEST
Function selectors
Warning:
Custom made settings will be lost when this option is used!
If the batteries are removed for more than 1 minute the custom made settings will
be lost.
The default setup is listed below:
Instrument setting
Contrast
Isc factor (except in UK version) 1.00
Z factor (UK version only)
RCD standards
Language
Function
Sub-function
Z - LINE
Z - LOOP
Zs
rcd
RCD
Note:
Initial settings (reset of the instrument) can be recalled also if the TAB key is
pressed while the instrument is switched on.
Restores default settings.
Exits back to main function menu without changes.
Default value
As defined and stored by adjustment procedure
0.8
EN 61008 / EN 61009
English
Parameters / limit value
Fuse type: none selected
Fuse type: none selected
Fuse type: none selected
RCD t
Nominal differential current: I
RCD type: G
Test current starting polarity:
Limit contact voltage: 50 V
Current multiplier: 1
Figure 4.3: Initial settings dialogue
N
20
Settings
=30 mA
(0)