METREL MI 3122 Instruction Manual page 29

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD
Step 5
Step 7
Displayed results:
x1 ....... Step 1 trip-out time (
x1 ....... Step 2 trip-out time (
x5 ....... Step 3 trip-out time (
x5 ....... Step 4 trip-out time (
x½ ...... Step 5 trip-out time (
x½ ...... Step 6 trip-out time (
I ........ Step 7 trip-out current (0º),
I ........ Step 8 trip-out current (180º),
Uc ....... Contact voltage for rated I  N.
Notes:
The autotest sequence is immediately stopped if any incorrect condition is detected,
e.g. excessive Uc or trip-out time out of bounds.
Auto test is finished without x5 tests in case of testing the RCD type A with rated
residual currents of I  n = 300 mA, 500 mA, and 1000 mA. In this case auto test
result passes if all other results pass, and indications for x5 are omitted.
Tests for sensitivity (I
Figure 5.6: Individual steps in RCD autotest
Top
Figure 5.7: Two parts of result field in RCD autotest
, I  N, 0º),
, I  N, 180º),
, 5  I  N, 0º),
, 5  I  N, 180º),
, ½  I  N, 0º),
, ½  I  N, 180º),
, steps 7 and 8) are omitted for selective type RCD.
29
Testing RCD
Step 6
Step 8
Bottom

Hide quick links: