METREL MI 3122 Instruction Manual page 58

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD
Modifications of the chapter 5.2
Modified test parameters for fault loop impedance measurement
Fuse type
Selection of fuse type [---, FUSE, B, C, D]
Lim
High limit fault loop impedance value for selected fuse.
See Appendix A.3 for reference fuse data.
Figure 5.10: Examples of loop impedance measurement result
Displayed results:
Z fault loop impedance
Isc ........... prospective fault current,
Lim .......... high limit fault loop impedance value.
Prospective fault current I
where:
Un
Nominal U
L-PE
scalling_factor ...... Correction factor for Isc (set to 1.00).
Modifications of the chapter 5.3
Modified test parameters for line impedance measurement
Fuse type
Selection of fuse type [---, FUSE, B, C, D]
Lim
High limit line impedance value for selected fuse.
See Appendix A.3 for reference fuse data.
Line to neutral
Figure 5.13: Examples of line impedance measurement result
Displayed results:
is calculated from measured impedance as follows:
PFC
I
PFC
Z
L
PE
voltage (see table below),
U
Input voltage range (L-PE)
n
110 V
(93 V  U
230 V
(185 V  U
Appendix C – Country notes
U
N
scaling
_
factor
 134 V)
L-PE
 266 V)
L-PE
Line to line
58