MI 3122 Smartec Z Line-Loop / RCD
8 Technical specifications
8.1 RCD testing
8.1.1 General data
Nominal residual current (A,AC) ....... 10 mA, 30 mA, 100 mA, 300 mA, 500 mA,
Nominal residual current accuracy .... -0 / +0.1 I ; I = I N, 2 I N, 5 I N
Test current shape ............................ Sine-wave (AC), pulsed (A)
DC offset for pulsed test current ....... 6 mA (typical)
RCD type .......................................... G (non-delayed), S (time-delayed)
Test current starting polarity ............. 0 º or 180 º
Voltage range ................................... 50 V 264 V (45 Hz 65 Hz)
RCD test current selection (r.m.s. value calculated to 20ms) according to IEC 61009:
I N × 1/2
I N (mA)
AC
10
5
30
15
100
50
300
150
500
250
1000
500
n.a. .................................................... not applicable
AC type ............................................. sine wave test current
A type...... ........................................ pulsed current
8.1.2 Contact voltage RCD-Uc
Measuring range according to EN61557 is 20.0 V 31.0V for limit contact voltage 25V
Measuring range according to EN61557 is 20.0 V 62.0V for limit contact voltage 50V
Measuring range (V)
0.0 19.9
20.0 99.9
The accuracy is valid if mains voltage is stabile during the measurement and PE terminal
is free of interfering voltages.
Test current ....................................... max. 0.5 I
Limit contact voltage ......................... 25 V, 50 V
Specified accuracy is valid for complete operating range.
1000 mA
-0.1 I / +0; I = 0.5 I N
AS / NZ selected: ± 5 %
I N × 1
A
AC
A
3.5
10
20
10.5
30
42
35
100
141
105
300
424
175
500
707
350
1000
1410
Resolution (V)
0.1
I N × 2
I N × 5
AC
A
AC
20
40
50
60
84
150
200
282
500
600
848
1500
1000
1410
2500
2000
n.a.
n.a.
Accuracy
(-0 % / +15 %) of reading ± 10 digits
(-0 % / +15 %) of reading
N
46
Technical specifications
RCD I
A
AC
100
212
707
n.a.
n.a.
n.a.
A