Trip-Out Time (Rcdt) - METREL MI 3122 Instruction Manual

Z line-loop / rcd
Table of Contents

Advertisement

MI 3122 Smartec Z Line-Loop / RCD
Loop resistance is indicative and calculated from Uc result (without additional proportional
factors) according to:
Figure 5.3: Example of contact voltage measurement results
Displayed results:
Uc ....... Contact voltage.
Rl ........ Fault loop resistance.
Rmax .. Maximum earth fault loop resistance value according to BS 7671.

5.1.2 Trip-out time (RCDt)

Trip-out time measurement verifies the sensitivity of the RCD at different residual currents.
Trip-out time measurement procedure
Select the
RCD
Set sub-function RCDt.
Set test parameters (if necessary).
Connect test cable to the top of the instrument.
Connect test leads to the item to be tested (see figure 5.2 ).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional).
Figure 5.4: Example of trip-out time measurement results
Displayed results:
t .......... Trip-out time,
Uc ....... Contact voltage for rated I
U
.
C
R
L
I
N
function using the function selector switch.
N
.
26
Testing RCD