MI 3122 Smartec Z Line-Loop / RCD
Prospective short-circuit current (calculated value)
Measuring range (A)
0.00 0.99
1.0 99.9
100 999
1.00k 99.99k
100k 199k
Test current (at 230 V) ...................... 6.5 A (10 ms)
Nominal voltage range ...................... 30 V 500 V (45 Hz 65 Hz)
8.4 Voltage, frequency, and phase rotation
8.4.1 Phase rotation
Nominal system voltage range .......... 100 V
Nominal frequency range .................. 15 Hz 500 Hz
Result displayed ............................... 1.2.3 or 3.2.1
8.4.2 Voltage
Measuring range (V)
0 550
Result type ........................................ True r.m.s. (trms)
Nominal frequency range .................. 0 Hz, 15 Hz 500 Hz
8.4.3 Frequency
Measuring range (Hz)
15.0 499.9
Nominal voltage range ...................... 20 V 550 V
8.5 Online terminal voltage monitor
Measuring range (V)
0 550
Resolution (A)
0.01
0.1
1
10
1000
550 V
AC
Resolution (V)
1
Resolution (Hz)
0.1
Resolution (V)
1
49
Technical specifications
Accuracy
Consider accuracy of line
resistance measurement
AC
Accuracy
(2 % of reading + 2 digits)
Accuracy
(0.2 % of reading + 1 digit)
Accuracy
(2 % of reading + 2 digits)