MI 3122 Smartec Z Line-Loop / RCD
RCD autotest procedure
RCD Autotest steps
Select the
RCD
Set sub-function AUTO.
Set test parameters (if necessary).
Connect test cable to the top of the instrument.
Connect test leads to the item to be tested (see figure 5.2 ).
Press the TEST key to perform the test.
, 0 (step 1).
Test with I
N
Re-activate RCD.
, 180 (step 2).
Test with I
N
Re-activate RCD.
Test with 5 I
, 0 (step 3).
N
Re-activate RCD.
Test with 5 I
, 180 (step 4).
N
Re-activate RCD.
Test with ½ I N, 0 (step 5).
Test with ½ I N, 180 (step 6).
Trip-out current test, 0 (step 7).
Re-activate RCD.
Trip-out current test, 180 (step 8).
Re-activate RCD.
Store the result by pressing the MEM key (optional).
Result examples:
Step 1
Step 3
function using the function selector switch.
28
Testing RCD
Notes
Start of test
RCD should trip-out
RCD should trip-out
RCD should trip-out
RCD should trip-out
RCD should not trip-out
RCD should not trip-out
RCD should trip-out
RCD should trip-out
End of test
Step 2
Step 4