DAMA-SM-21-003
4.18 Position Sensor Abnormality
H6
Error Code
Description
Position Sensor Abnormality
Method of Error
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Detection
The compressor fails to start in about 15 seconds after the compressor run command signal
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Power supply voltage out of specification
Supposed
Disconnection of the compressor harness
Causes
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage out of specified range
Troubleshooting
Reference
Check No.18 Refer to P.89
Reference
Check No.20 Refer to P.90
Service Diagnosis
is sent.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Turn off the power.
Check the power supply voltage.
NO
Voltage as rated?
YES
Check No. 18
Check the discharge pressure.
NO
OK?
YES
Check No. 20
Check the short circuit of the
diode bridge.
NO
Normal?
YES
Check the connection.
Electrical
components or
NO
compressor harnesses
connected as
specified?
YES
Correct the power supply.
Replace the stop valve.
Replace the outdoor
unit PCB (main PCB).
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB (main PCB) / compressor
Troubleshooting