Position Sensor Abnormality - Daikin RXL-W Series Service Manual

Inverter pair
Table of Contents

Advertisement

SiUS092231E

7.13 Position Sensor Abnormality

H6
Error Code
Method of Error
A compressor start-up failure is detected by checking the compressor running condition through the
Detection
position detection circuit.
Error Decision
 If the error repeats, the system is shut down.
Conditions
 Reset condition: Continuous run for about 11 minutes without any other error
Supposed
 Power supply voltage out of specification
Causes
 Disconnection of the compressor harness
 Defective compressor
 Defective outdoor unit PCB
 Start-up failure caused by the closed stop valve
 Input voltage outside the specified range
Part 6 Service Diagnosis
Troubleshooting for Outdoor Unit
174

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents