Tab.35
Electrical connections to be bridged on CB-01
Producer
Connection
B
CB-01
(1)
BL
(1) Bridge: These connectors must be bridged. Some bridges are already factory-fitted, some need to be fitted for this specific installation
example.
Tab.36
Parameters to be set
Producer
Connection
CU-GH13
(1)
AP102 = 0
CP020 = 0
DP007 = 0
(1) Parameters to be set: The parameters are separated per PCB, and must be set on that specific PCB.
Tab.37
Parameter list
Code
Display text
AP102
Boiler Pump function
CP020
Zone Function
DP007
Dhw 3wv Standby
CP021
Zone Function
CP020
Zone Function
6
Settings
6.1
Introduction to parameter codes
Fig.46
Code on a HMI T-control
00:12
......
........ .......
......
....................
..... ... ....... .... .. ..... ....
....... .... .. ..... ....
....... ...........
CP010
..... ... ....... ....
..... ... ....... ....
..... ... ....... .... .. ..... ....... .... ..... .......
........ .......
Fig.47
First letter
7734325 - v.07 - 22092022
CH 1 / CircB 1
CH 1 / CircB 1
SCB-02
CP021 = 1
Menu path
> Installation Setup > CU-GH13 > Gas fired appliance >
Parameters, counters, signals > Parameters > General
> Installation Setup > CU-GH13 > CIRCA > Parameters,
counters, signals > Parameters > General
> Installation Setup > CU-GH13 > Internal DHW > Parameters,
counters, signals > Parameters > General
> Installation Setup > SCB-02 > CH 1 > Parameters, counters,
signals > Parameters > General
> Installation Setup > SCB-02 > DHW 1 > Parameters,
counters, signals > Parameters > General
The controls platform makes use of an advanced system to categorise
parameters, measurements and counters. Knowing the logic behind these
codes, makes it easier to identify them. The code consists of two letters
and three numbers.
.........
.......
...
......
.....
CP010
AD-3001373-02
The first letter is the category the code relates to.
CP010
A
C
AD-3001375-01
D
E
G
P
Category D codes are appliance controlled only. When the domestic hot
water is controlled by an SCB, it is handled like a circuit, with C-category
codes.
DHW 1
DHW 1
SCB-02
CP020 = 6
Appliance: Appliance
Circuit: Zone
Domestic hot water: Domestic hot water
External: External options
Gas fired: Gas-fired heat engine
Producer: Central heating
6 Settings
Set to
0 = No
0 = Disable
0 = CH position
1 = Direct
6 = DHW tank
31