7.2.3
Programming boiler control
Set the integrated control in compliance with the corresponding
operating instructions.
7.2.4
Instruct the user of the boiler
7.2.5
Shut-down
Temporary shut-down with frost protection
- Do not isolate the electric power supply.
- Do not close the gas cock.
- Use the switch function - sets controls to off: use
-symbol.
See chapter 4.1.3
Permanent shut-down without frost protection
- Set system controls to off.
- Isolate the electric power supply.
- Close the gas cock.
- Drain the system.
26/01/2009 - 300014883-001-F
If the values exceed the tolerances:
Check the gas input pressure.
Check that the restrictor fitted is suitable for the gas being
used (G20 = diameter 8.6, Propane = 6.7).
-key and