INSTALLATION INFORMATION

Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can
result in death, fire, or electrical shock.
IMPORTANT: Connect PTAC/PTHP to a
single-outlet circuit only.
230/208 VOLT PTAC/PTHP
All 230/208 volt PTAC/PTHPs are equipped
with power cords.
230/208 volt
250 volt Receptacles and
PTAC/PTHP
Overcurrent Protection
AMPS
15
RECEPTACLE
NEMA Type
6-15R
The field-supplied outlet must match plug on
service cord and be within reach of service
cord.

ELECTRICAL REQUIREMENTS

20
30
6-20R
6-30R
Electrical Shock Hazard
Electrically ground PTAC/PTHP.
Connect ground wire to green pigtail lead.
Use copper wire for supply connection.
Correct wire gauge is shown in the chart
below.
Failure to follow these instructions can
result in death or electrical shock.
Rating Plate Ampacity
Less than 15
16 - 20
21 - 30
265 VOLT PTAC/PTHP
All 265 volt PTAC/PTHPs are equipped with
pigtail leads for field wiring.
IMPORTANT:
• Use copper conductors only.
• Wire sizes are per NEC.
• Use on individual branch circuit only.
• Use overcurrent protection indicated on
PTAC/PTHP's rating plate.
• PTAC/PTHP must be grounded to branch
circuit.
• Check local codes.
2-1
AWG
14
12
10