8-22. Common to All Models

1. The Self-Diagnosis Function Display and What is Detected
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is
connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to
Test Run or servicing materials.
Communication error in the remote control
circuit
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
Operation of indoor protection device
Operation of outdoor protection device
Error in the indoor thermistor
Error in the outdoor thermistor
Error in the indoor EEPROM
Error in the outdoor EEPROM
Error related to the compressor
Error in indoor settings
Error in outdoor settings
Inconsistency in Air/Heat (Including an auto-temp setting for a model without
auto-temp settings)
Oil Alarm (Same as operation of outdoor protection device)
Test Run
When using CZ-RWSC2
If you have either an outdoor maintenance remote control or
a wired remote control and a service checker special wiring
(623 178 5082: for service use) at hand, you can get more
detailed information about an alarm by connecting one to the service
connecter as in the diagram. For information such as how to connect
to receivers, etc., refer to the Users Manual that came attached with
the service checker special wiring.
2. Room Temperature Sensor Settings
Common to All Models
The indoor unit and the wireless remote control are equipped with
indoor temperature sensors. The sensing of indoor temperature
works via one of them.
When the unit is shipped, it is set to the indoor unit, but to switch
8
to the remote control, press the sensor button (diagram at right)
inside the remote control's cover and then check to make sure that
Main Sensor on the LCD screen goes off.
NOTE
Even when the Sensor switch has been set to the remote
control, if the unit does not receive any room temperature
data from the remote control for ten minutes, it automatically
switches back to the indoor unit sensor, so be sure to install
the remote control facing the receiver.
Error Detected
Alarm Display
E01–E03, E08–E14, E17, E18
E04–E07, E15, E16, E19–E31
P01, P09–P14
P02–P08, P15–P31
F01–F03, F10–F11
F04–F09, F12–F28
F29
F30, F31
H01–H31
L01–L03 L05–L09
L04, L10–L31
WL Remote Control LED Displa
Run
Timer
: Off /
: On /
Service
Connector
8-30
y
Standby
Blinking
Alternately
Alternately
Alternately
Alternately
Simultaneously
Simultaneously
Simultaneously
Simultaneously
Alternately
Alternately
Simultaneously
: Blinking (0.5 sec. intervals)
Fig. 8-36
Sensor Button
Fig. 8-37