Panasonic S-45PU1E5 Technical Data & Service Manual page 191

Inverter r410a
Table of Contents

Advertisement

300 mm or less
0 - 45°
* Length of supplied drain hose = 140 mm
Do not use natural drainage.
Do not install the pipe with an upward gradient from the
connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.
(Fig. 2-9)
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to the
unit. Fasten the pipe to a wall, frame, or other support as
close to the unit as possible. (Fig. 2-10)
Provide insulation for any pipes that are run indoors.
Checking the Drainage
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up spilled
water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour about 500 cc of water into the drain pan to
check drainage. (Fig. 2-11)
Over
100 mm
Plastic container
for water intake
Water
(Approx. 500 cc)
(3) Short the check pin (CHK) on the indoor control board and
operate the drain pump. Check the water flow through the
transparent drain pipe and see if there is any leakage.
(4) When the check of drainage is complete, open the check
pin (CHK) and remount the tube cover.
CAUTION
Be careful since the fan will start when you short the pin on
the indoor control board.
850 mm or less
Fig. 2-8
Uphill slope
Fig. 2-9
Support
bracket
Fig. 2-10
Water drain
Drain pan outlet
Fig. 2-11
(4-Way Cassette 60 × 60)
Part Name
Washer
Flare
insulation
Insulation tie
Vinyl tie
Drain hose
insulation
Full-scale
installation
diagram
Washer head
screw
Drain hose
Hose band
Use M10 for suspension bolts.
Field supply for suspension bolts and nuts.
1-185
Figure
Q'ty
Remarks
For temporarily
8
suspending indoor
unit from ceiling
T3
2
For gas / liquid
T5
set
tube connection
For gas / liquid
2
tube / flare nut
connection
For flare /
8
drain insulating
connection
For drain tube
T10
1
connection
Printed on
1
container box
For full-scale
4
installation diagram
For unit & PVC
1
tube connection
L140
For drain hose
2
connection
1

Hide quick links:

Advertisement

Table of Contents