E07 Outdoor unit sending failure to indoor unit
1.
Error Detection Method
It is judged an error when a unit itself cannot receive (discrepancy) a signal within a 3-minute period that it had sent.
Outdoor main PC board error
The setting of the terminal resistor select switch on the outdoor main PC board is set incorrectly.
2.
Error Diagnosis
Is the indoor/outdoor operation line connected to more than one
1 Outdoor
1-1
outdoor unit? (Network wired?)
unit
control
Is the SHORT on the terminal resistor switch on the outdoor main
PC board
1-2
PC board set to one unit, and the others are OPEN?
Is the terminal resistor select switch on the outdoor main PC board
1-3
set to OPEN?
1-4
Is the indoor/outdoor operation line opened or shorted?
1-5
Replace the outdoor unit main PC board.
For information on the procedures for replacing the outdoor main PC board, refer to the manual that is packaged with the
service board.
A746894 : (U-60PE1E5, U-71PE1E5)
(for single-phase outdoor unit PCB)
TERMINAL EEPROM
A746845 : (U-125PE1E5, U-140PE1E5)
(for single-phase outdoor unit PCB)
TERMINAL
EEPROM
5-17
A746844 : (U-100PE1E5)
(for single-phase outdoor unit PCB)
TERMINAL
A746967 : (U-100PE1E8, U-125PE1E8, U-140PE1E8)
(for 3-phase outdoor unit PCB)
TERMINAL
Yes
1-2
No
1-3
Yes
1-4
Set the SHORT to
No
one unit only
Make the SHORT
Yes
setting
No
1-4
Yes
Correct the wiring
No
1-5
EEPROM
EEPROM
5