Panasonic S-45PU1E5 Technical Data & Service Manual page 306

Inverter r410a
Table of Contents

Advertisement

H03 Primary current CT sensor (current sensor) failure
1.
Error Detection Method
It is judged an error based on the criteria listed below.
If 18A or greater is detected when the compressor is stopped (alarm triggered even if the connector is unplugged).
If no current is detected even though a compressor is running.
2.
Error Diagnosis
1 Check the
1-1
control
PC board
5
Turn the power on again and run the outdoor unit.
Is alarm occurred after operation?
5-34
Yes
Replace CR board.
No
See what happens.