4-3. Automatic Fan Speed Control

The indoor fan mode is controlled as shown below during the automatic fan mode.
The fan mode does not change for 3 minutes during cooling operation and 1 minute during heating
operation once it is changed.
The values in the parenthesis are when the remote controller sensor is enabled.
Cooling
(deg)
+3
+2
+1
Set temp.
Indoor fan mode HH
L
H
HH
H
4-5
Heating
(deg)
Set temp.
(-1)-2
(-2)-4
Indoor fan mode HH
H
L
H
HH
4