Panasonic S-45PU1E5 Technical Data & Service Manual page 198

Inverter r410a
Table of Contents

Advertisement

1
Unit
Washer
(supplied)
b) Lift the indoor unit, and place it on the washers through
the notches, in order to fix it in place. (Fig. 3-14)
c) Tighten the 2 hexagonal nuts on each suspension bolt to
suspend the indoor unit as shown in Fig. 3-15.
NOT E
The ceiling surface is not always level. Confirm that the indoor
unit is evenly suspended. For the installation to be correct,
leave a clearance of about 10 mm between the ceiling panel
and the ceiling surface and fill the gap with an appropriate
insulation or filler material.
(8) If the tubing and wiring are to go towards the rear of the
unit, make holes in the wall. (Fig. 3-16)
(9) Measure the thickness of the wall from the inside to the
outside and cut PVC pipe at a slight angle to fit. Insert the
PVC pipe in the wall. (Fig. 3-17)
NOT E
The hole should be made at a slight downward slant to the
outside.
Suspension bolt
(field supply)
Washer
(field supply)
Washer (supplied)
Double nut
(field supply)
Ceiling
surface
Nut
(field supply)
Suspension bolt
Indoor
Outdoor
side
side
PVC pipe (field supply)
Cut at slight angle
Fig. 3-12
Duct for Fresh Air
There is a duct connection port (knock-out hole) at the right-rear
of the top panel of the indoor unit for drawing in fresh air. If it
is necessary to draw in fresh air, remove the cover by opening
the hole and connecting the duct to the indoor unit through the
connection port. (Fig. 3-18)
Fig. 3-13
Remote controller wiring inlet port
(ø30, rubber grommet on right side only)
Shaping the Tubing
Fig. 3-14
The positions of the refrigerant tubing connections are
shown in the figure below. (The tubing can be routed in 3
directions.) (Fig. 3-19)
* When routing the tubing out through the top or right sides,
knock out the appropriate parts in the top panel and cut
notches in the side panel (Fig. 3-18).
* When routing the tubing out through the top, the optional
L-shape tubing kit is required.
Fig. 3-15
If the tubing is to be routed out together, use a box cutter or
similar tool to cut out the part of the rear cover indicated by
the marked area (Fig. 3-20), to match the positions of the
tubes. Then draw out the tubing.
Fig. 3-16
1-192
INSIDE
OUTSIDE
Wall
PVC pipe
Slight
angle
Outside air intake duct connection
port (ø100, knock-out)
Power inlet port
(ø40, knock-out)
Rear outlet port
Left-side drain
hose outlet port
Rear cover
Fig. 3-17
Unit: mm
Fig. 3-18
Fig. 3-19
Fig. 3-20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents