Panasonic S-45PU1E5 Technical Data & Service Manual page 220

Inverter r410a
Table of Contents

Advertisement

1
SELECTING THE LOCATION FOR THE INDOOR UNIT
Required Minimum Space for Installation and Service.
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
Top view
(Unit:mm)
If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
POSITION OF SUPENSION BOLT
A
B
Table 6-1
A
S-F36PN1E5
S-F45PN1E5
840
S-F50PN1E5
S-F60PN1E5
1060 1000
S-F71PN1E5
S-F100PN1E5
1260 1200
S-F125PN1E5
S-F140PN1E5
Control box
Inspection hole
(600 x 600)
600
<Front>
600
(unit: mm)
B
C
D
E
780
523
64
650
523
64
650
523
64
650
Front view
Above 250cm
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
!
Caution
Remove the absorber at air return hole
before installation.
Absorber
1-214
1~3mm
Drainage hole
Fig. 6-1
Fig. 6-1.1