P13 Alarm valve open
1.
Error Detection Method
Detection is performed only in the test run. When once detected or the test run finished without any error,
the second detection will not be done.
In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the
following conditions.
The status of small temperature change of the oprating indoor unit continues for 3 minutes even after 5-minute to
15-minute since the cooling test run has started.
The status of small temperature change of the oprating indoor unit continues for 3minutes even after 7-minute to
15-minute since the heating test run has started.
2.
Error Diagnosis
1 Service
valve
1-1
Service valve inside the outdoor unit closed
2 Adjustment
to
2-1
Not additional refrigerant charged
refrigerant
change
3 Blockage
3-1
Are the tubes clogged?
in
refrigerant
circuit
Is the outdoor unit's electronic control valve operating correctly?
3-2
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
3-3 As the second detection is not done, restart and see what happens if there is no error.
5-47
Open the service
Yes
valve
No
2-1
Additional
Yes
refrigerant charge
No
3-1
Yes
Avoid clogging
No
3-2
Yes
3-3
Replace the
No
electronic control
valve