List of Item Codes (Some item codes cannot be set due to the type of models.)
Item code
01
Control system schedule
02
Control system schedule
03
Control system schedule
04
Snowfall sensor operation
05
Control system schedule
06
Control system schedule
07
Ignore capacity
08
Control system schedule
09
Control system schedule
0A
Control system schedule
0b
Control system schedule
0C
Forced operation of
indoor unit drain pump
0d
Control system schedule
0E
Cooling only
0F
Control system schedule
10
Control system schedule
11
Multi-fl oor installation
12
Control system schedule
6
13
Control system schedule
20
Cool OL control
50
Demand 1
51
Demand 2
52
Current control level
57
Silent mode
58
Silent mode starting time (hour)
59
Silent mode starting time (minute)
5A
Silent mode fi nishing time (hour)
5B
Silent mode fi nishing time (minute)
Do not set
Do not set
Do not set
0 = No sensor, control performed
1 = No sensor, control not performed
2 = Sensor present, control performed
3 = Sensor present, control not performed
Do not set
Do not set
0 = Disabled
Do not set
Do not set
Do not set
Do not set
0 = Disabled
1 = During cooling only, 2 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = During cooling only, 4 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
3 =At all times, 4 hours stopped + 20 minutes operating
4 =At all times, 2 hours stopped + 20 minutes operating
Do not set
0 = Heat pump
Do not set
Do not set
0 = Non
Do not set
Do not set
Do not set
70% ~ 100% (40% ~ 160% setting capable)
70% ~ 100% (40% ~ 160% setting capable)
70% ~ 100% , -1 (No control) (40% ~ 160% setting capable)
0 = Normal (at shipment)
22 = 22 o'clock (at shipment)
00 = 00 minute (at shipment)
08 = 8 o'clock (at shipment)
00 = 00 minute (at shipment)
* Figures in parentheses indicate the data at the time of shipment from the factory.
6-8
Parameter
1 = Ignores capacity ratio
1 = Cooling only
1 = Available
1 = Auto silent
2 = Capacity priority