Thermostats
Other Digital Joins
Signal Name
GLOBAL_UPDATE_BTN
MESSAGE_ICON_ON
FRONT_PANEL_LOCKOUT
RUN_BACKLIGHT
BTN_PRESS_1_F
BTN_PRESS_2_F
BTN_PRESS_3_F
BTN_PRESS_4_F
MSG_WAITING_F
Humidifier Related Joins (all analog values are in whole %)
Signal Name
HUMIDIFIER_EN
HUMIDIFIER_EN_F
HUM_SETPOINT
HUM_SETPOINT_F
OUTDOOR_HUM
OUTDOOR_HUM_F
INDOOR_HUM
28 • Thermostats: CHV-TSTAT and CHV-THSTAT
Crestron CHV-TSTAT and CHV-THSTAT
Symbol
I/O
Advanced
Input
Advanced
Input
Both
Input
Advanced
Input
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
NOTE: All humidity-related analog values are input and output as whole numbers.
Example: For 47% humidity, the reading is sent as 47.
Symbol
I/O
Both
Input
Both
Output
Both
Input
Both
Output
Both
Input
Both
Output
Both
Input
Definition
Output that is asserted when the global update "send"
button is pressed
Causes the front panel third text line to flash "view msg"
alternately with "on line/offline," alerting the user to
check a message that was sent to the thermostat
Causes the buttons on the thermostat to become
inoperable when asserted, Useful for locking out
changes in operation by users
Triggers the backlight to turn on for its 8 seconds
Asserted for the duration that remote button 1 is pressed
(up button, remote page 1)
Asserted for the duration that remote button 2 is pressed
(down button, remote page 1)
Asserted for the duration that remote button 3 is pressed
(up button, remote page 2)
Asserted for the duration that remote button 4 is pressed
(down button, remote page 2)
Asserted when an indirect text message is received on
$message join and latched until the user presses the
"CLR" button on the message screen
Definition
Enables the humidistat operations when asserted
(Digital)
Feedback for above (Digital)
Analog join that sets the humidity setpoint, 5-70%, all
other values ignored, All values are whole numbers, so
sending 38 changes the setpoint to 38%
Feedback output so that changes in the value can be
monitored by the control system
Input allowing the outdoor humidity value to be
displayed on the "outdoor" page even if the particular
unit does not have an outdoor remote sensor
Output for outdoor humidity It is only active when a
particular unit has a remote outdoor sensor connected
Otherwise, zero is output
Input allowing display of indoor humidity on the front
panel Importing the value this way is required only if
setup was a TSTAT with non-humidity remotes (no way
of measuring indoor humidity) The network input value
is overridden by a measured value if one is available