Signal Name
DUAL_FUEL_HP_F
RADIANT_F
FAN_IN_HEAT_F
HEAT_1_STG_F
HEAT_2_STG_F
COOL_1_STG_F
COOL_2_STG_F
TEMP_IN_F
TEMP_IN_C
DISP_FP_HUM_F
DISP_FP_OD_F
DISP_HUM_F
DISP_GLOBAL_F
DISP_OUTDOOR_F
DISP_REM_BUTTONS1_F
DISP_REM_BUTTONS2_F
DUAL_SP_AUTO_MODE_F
LOW_TEMP_HUM_COMP_F
Sensor Setup Related Digital Joins
Signal Name
USE_LOC_TEMP_F
USE_R1_TEMP_F
USE_R2_TEMP_F
OMIT_LOC_TEMP_F
OMIT_R1_TEMP_F
OMIT_R2_TEMP_F
R1_T_OUTDOOR_F
R2_T_OUTDOOR_F
USE_LOC_HUM_F
USE_R1_HUM_F
USE_R2_HUM_F
Operations and Installation Guide - DOC. 8163
Symbol
I/O
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Symbol
I/O
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Advanced
Output
Definition
Asserted when dual-fuel heat pump system declared, In
conventional heat pump systems, aux heat may be
used to supplement heat pump heat, In dual-fuel
setups, the aux heat output runs in place of the heat
pump in cold weather Requires outdoor temperature
source
Asserted when a heat/cool system is declared as
Radiant, Radiant systems require slightly different
control characteristics than forced air systems
Asserted when "Run Fan in Heat" is "yes", Most heating
systems control the fan if it is needed, but some
systems may require the fan to be controlled by the
thermostat
Asserted when one stage of heat is defined
Asserted when two stages of heat are define
Asserted when one stage of cooling is defined
Asserted when two stages of cooling are defined
Asserted when Fahrenheit units are used
Asserted when Celsius units are used
Asserted when front panel object is set to be humidity
Asserted when front panel object is outdoor temperature
Asserted when humidity pages are enabled
Asserted when global update page is enabled
Asserted when outdoor page is enabled
Asserted when remote button page 1 is enabled
Asserted when remote button page 2 is enabled
Asserted when using 2 point auto mode, unasserted
means using single point auto mode
Asserted when low temperature humidity compensation
is enabled, helps prevent condensation on windows in
cold weather
Definition
Asserted when using built in temperature sensor
Asserted when using remote 1 temperature sensor
Asserted when using remote 2 temperature sensor
Asserted when Omitting built in temperature sensor
Asserted when Omitting remote 1 temperature sensor
Asserted when Omitting remote 2 temperature sensor
Asserted when remote 1 temperature sensor has been
declared as outdoor (OD)
Asserted when remote 2 temperature sensor has been
declared as outdoor (OD)
Asserted when using built in humidity sensor (THSTAT)
Asserted when using remote 1 humidity sensor
Asserted when using remote 2 humidity sensor